Vortex flowmeter verification detection method
Standard table method
The vortex flowmeter is used as a standard device in series with the flowmeter to be inspected, and can be verified by static method or dynamic method. By comparing the readings of the two flow meters, the error of the vortex flowmeter to be tested is obtained.
Standard table flow meter standard device features:
1. Standard table method is suitable for measuring various fluids (including liquids and gases), and also for liquids of various viscosities.
2. The indication value is checked. The flow meter used as the standard meter is installed in series with the flowmeter to be tested in the same closed pipeline system. Generally, there is no time measurement error.
3. As a standard table, the vortex flowmeter can be the same as or different from the flowmeter to be tested.
4. When the flow meter is verified by the standard meter method, the airflow or liquid flow can be not cut off, so it is suitable for online verification, and is also suitable for the measurement standard for the closed pipeline. 5, the standard table method is easy to achieve automation, sealed and safe, does not pollute the environment.
6. Small size, light weight, simple device structure, convenient operation, easy transportation and installation, and low cost.
7. Standard meter flowmeters have low accuracy and poor stability, and often need to be compared regularly or irregularly to monitor their metering performance. The standard table has a shorter verification period.
Advantages of turbine flow meters
The pressure loss is small, and the impeller has anti-corrosion function;
1.Adopt advanced ultra-low power single-chip microcomputer technology, the whole machine has strong functions, low power consumption and superior performance.
2.Intelligent flow display with nonlinear accuracy compensation. Correction formula accuracy is better than ±0.02%
3.The meter factor can be set online by button and can be displayed on the LCD screen. The LCD screen is intuitive and clear, and the reliability is strong.
4.EEPROM is used to accumulate the flow and the meter coefficient is powered down. The protection time is more than 10 years.
5.Using high-performance MCU central processing unit to complete data acquisition and processing display output, cumulative flow instantaneous flow
6.The screen displays a convenient man-machine interface for data transfer in standard 485 format.
7.Fully hard alloy (tungsten carbide) shielded cantilever beam structure bearing, integrating rotary bearing and pressure bearing, greatly improving bearing life and working in medium with a small amount of sediment and dirt.
8.It adopts 1Cr18Ni9Ti all stainless steel structure (the turbine adopts 2Cr13) and has good anti-corrosion performance.
9.Easy to maintain, self-rectifying structure, small and light, simple structure, which can be combined in a short time.
10.Internal cleaning is simple.
11.Strong anti-magnetic interference and vibration capability, reliable performance and long life
12.The lower limit flow rate is low and the measuring range is wide.
13.The on-site display type LCD screen is clear and intuitive, with low power consumption. The 3V lithium battery can be operated continuously for more than 5 years.
Corrosion resistant, suitable for acid and alkali solutions
Battery powered electromagnetic flowmeter features
1. Micro power consumption design, five 3.6V lithium batteries, continuous operation for 5~10 years, and easy to replace the battery.
2. The display adopts LCD large-screen liquid crystal display, which can display multiple flow parameters such as instantaneous flow rate, flow rate (pipe pressure), cumulative total amount of forward and reverse, and alarm prompt.
3. There are no movable and resistance parts in the measuring tube, no entanglement or clogging phenomenon, almost no pressure loss, and long-term reliable and continuous work.
4. Wide measurement range: The flow rate measurement range can reach 0.05m/s~10m/s.
5. High measurement accuracy: ±0.5% ~ ±1.0%.
6. Measurement stability: The measurement accuracy is not affected by changes in physical parameters such as temperature, pressure, viscosity and density of the measured medium.
7, with pulse output and GSM wireless data remote transmission.
8, with data storage function, up to 1000 groups of traffic data can be saved, and the data storage time can be arbitrarily set and data query.