1. Measurements are not affected by changes in fluid density, viscosity, temperature, pressure, and conductivity;
2. There is no obstructed flow component in the measuring tube, no pressure loss, and the requirements of the straight pipe section are low. Unique adaptability to slurry measurement;
3. Reasonable selection of sensor lining and electrode materials, that is, good corrosion resistance and wear resistance;
4. The converter adopts novel excitation mode with low power consumption, stable zero point and high precision. The flow range can reach 150:1;
5. The converter can be integrated with the sensor or separated;
6. The converter adopts 16-bit high-performance microprocessor, 2x16LCD display, convenient parameter setting and reliable programming;
7. The flowmeter is a two-way measuring system with three totalizers: positive total, reverse total and total difference; can display positive and negative flow, and has multiple outputs: current, pulse, digital communication , HART;
8, the converter uses surface mount technology (SMT), with self-test and self-diagnosis function;
9. Measurement accuracy is not affected by changes in fluid density, viscosity, temperature, pressure and conductivity. The sensor induced voltage signal has a linear relationship with the average flow velocity, so the measurement accuracy is high.
10. There is no obstruction in the measuring pipe, so there is no additional pressure loss; there is no moving parts in the measuring pipe, so the life of the sensor is extremely long.
11. Since the induced voltage signal is formed in the entire space filled with the magnetic field and is the average value on the pipeline surface, the sensor requires a short straight pipe section and a pipe diameter of 5 times.
12. The converter adopts the latest and most advanced single-chip microcomputer (MCU) and surface mount technology (SMT) in the world. It has reliable performance, high precision, low power consumption, stable zero point and convenient parameter setting. Click on the Chinese display LCD to display the cumulative flow, instantaneous flow rate, flow rate, flow percentage, and more.
13, two-way measurement system, can measure forward flow, reverse flow. Special production technology and high-quality materials ensure that the performance of the product remains stable for a long time.
According to different output signals, these products can be divided into LWGY-□N type and LWGY-□A type.
LWGY-□N type sensor: 12~24VDC power supply, three-wire pulse output, high level ≥8V, low level ≤0.8V; signal transmission distance ≤1000m;
LWGY-□A type transmitter: 24VDC power supply, 2-wire 4-20mA output, signal transmission distance ≤1000.
This type of turbine flow products are divided into basic type and explosion-proof type (ExdIIBT6).
2, intelligent integrated turbine flowmeter
Intelligent integrated turbine flowmeter adopts advanced ultra-low-power single-chip microcomputer technology to develop a new intelligent instrument integrating turbine flow sensor and display integration. It adopts double-row liquid crystal field display, with compact structure, intuitive reading and reliability. High, free from external power interference, lightning strike, low cost and other obvious advantages. The instrument has three-point correction of the meter coefficient, the intelligent compensation meter coefficient is nonlinear, and field correction can be performed. The high-definition LCD displays both instantaneous flow (4 significant digits) and cumulative flow (8 significant digits with clear function). All valid data is not lost after 10 years of power failure. These turbine flowmeters are explosion-proof products with an explosion-proof rating of ExdIIBT6.
Second, choose from the type of flow meter
Various flow meters, such as volumetric flowmeters, speedmeters, and differential pressuremeters, have different characteristics. Different flowmeter types have different turndown ratios. The turbine flowmeter has a turndown ratio of 1:20 to 1:30, the Roots flowmeter has a turndown ratio of 1:20 to 1:160, and the film gauge has a turndown ratio of 1: 160 (The error characteristic curves of these three kinds of flow meters are shown in Figure 1), and the appropriate flow meter should be selected according to the actual situation.
By comparing the error characteristics of the above flowmeters, it can be seen that the starting flow of the membrane meter and the Roots flowmeter is small, the initial flow of the turbine meter is relatively large, and the membrane surface exhibits a positive deviation in the small flow state. The Roots flowmeter exhibits a negative deviation. At low flow rates, the gas supply company is more willing to select a membrane meter for metering.