Pvc Water Flow Meter

2020-05-27 06:12:05

Pvc Water Flow Meter

Choice of protection level
The protection level of the electromagnetic flowmeter should be selected according to the actual situation. If the sensor is required to be installed below the ground and is often flooded, IP68 should be selected. If the sensor is installed above the ground, IP65 and IP67 should be selected. In any case, the display area of ??the electromagnetic flowmeter cannot be used with water or enter the water, which may cause damage to the electromagnetic flowmeter. As a chemical company, the workshop produces high humidity, but IP65 (IP65 is a water-proof type. The electromagnetic flowmeter sensor housing allows the faucet to spray water from the sensor in any direction of the sensor of the electromagnetic flowmeter. The pressure of the water spray is 30Kpa, the water output It is 12.5L/S and the distance is 3 meters.) The electromagnetic flowmeter of the protection grade fully meets the requirements of on-site measurement.
Choice of connection method
Electromagnetic flowmeters have threaded connections, flanged connections, clamps, etc. In the chemical industry, flange-connected electromagnetic flowmeters are generally used. The selection must be consistent with the process-flange engineering pressure and standards.
Conclusion, with the maturity of the domestic instrument industry, chemical companies such as lithium carbonate, boric acid and potash will also enter the market in line with the domestic market. As an important industrial flow measuring instrument, electromagnetic flowmeter should play its role in DCS control. The right selection is especially important to provide accurate measurement data, reduce labor costs and increase production efficiency.

Pvc Water Flow Meter

First, the gas turbine flowmeter installation requirements
1. When the gas flowmeter is installed, it is strictly forbidden to directly conduct electric welding at the inlet and outlet flanges to avoid burning the internal parts of the flowmeter;
2. For the newly installed or overhauled pipeline, it must be purged to remove the debris in the pipeline before installing the flowmeter;
3. The gas turbine flowmeter should be installed in a place that is easy to maintain, has no strong electromagnetic field interference, no mechanical vibration and thermal radiation;
4. Gas turbine flowmeters should not be used in places where flow is frequently interrupted and there is strong pulsating flow or pressure pulsation;
5, the gas turbine flowmeter should ensure that the pipeline is coaxial, and prevent the gasket from protruding into the pipeline, otherwise it will disturb the flow profile;
6. The flow direction of the gas turbine flowmeter should be consistent with the direction marked on the casing. The upper and lower pipelines of the flowmeter should be guaranteed with 2DN and 1DN straight pipe sections;
7. When using external power supply, the flowmeter must have reliable grounding, but it should not share the grounding wire with the high-power system; when the pipeline is installed or repaired, the grounding wire of the welding system should not be overlapped with the flowmeter.
8. Since the flowmeter needs to be repaired and calibrated, in order to ensure normal gas supply, bypass piping should be set. The bypass pipe valve must be closed during normal use;
9. When constructing pipelines, it is advisable to install telescopic tubes or bellows to avoid serious stretching and causing breakage of the flowmeter;
10. When the gas turbine flowmeter is installed outdoors, the upper part should be covered to prevent the rainwater from immersing and the sun exposure affecting the service life of the flowmeter;
11. When installing the gas turbine flowmeter, it is advisable to add a filter to the flowmeter (filtering accuracy is recommended ≤20μm).
Second, gas turbine flowmeter requirements
1. When the gas turbine flowmeter is put into operation, the upstream valve of the flowmeter should be slowly opened (not less than 15 seconds), and then the downstream valve of the flowmeter should be slowly opened to prevent the instantaneous airflow from rushing to the turbine;
2. When the flowmeter needs to have a long-distance signal, it should be connected to the external power supply (+12~+24VDC) strictly according to the electrical performance index of the gas turbine flowmeter. It is strictly forbidden to directly connect 220VAC (or 380VAC) power supply at the signal output.

Pvc Water Flow Meter

Intelligent GPRS MAG flow meter working principle
Since the GPRS communication is a data packet communication network based on an IP address, after the monitoring center computer logs in to the Internet network, the IP address is assigned by the Internet, and each GPRS monitoring point establishes a connection with the host through the address and communicates. Each monitoring point collects data through the data acquisition module, processes the data through the embedded processor in the GPRS terminal, encapsulates the protocol, sends it to the GPRS network, and transmits it to the user data monitoring center computer.
Battery-powered converter GPRS communication introduction
The battery-powered converter with GPRS function can directly send data to the remote control center through the GPRS wireless module GPRS-DY or GPRS-DF, hereinafter referred to as the GPRS module, and then store the collected data in the database at regular intervals. Through the system, even in an off-site away from the observation site, it is convenient to collect and read data of each monitoring point, and truly realize the functions of remote monitoring and data sharing.